Nortel-networks 1000M Manual do Utilizador Página 67

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 474
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 66
Method for earthquake bracing 67
need help with where to place the fasteners on the backboard. In
each figure, the minimum (0.6 m by 1.8 m/2 ft by 6 ft) and maximum
(1.2 m by 2.4 m/4 ft by 8 ft) sizes of the backboard are used as
examples.
Figure 21 "Plywood fastener locations for wood and metal stud
walls, 16 inch spacing" (page 68) provides the fastener locations
for wood and metal stud walls with the minimum allowed stud
spacing of 0.4 m (16 in.).
Figure 22 "Plywood fastener locations for wood and metal stud
walls: 0.6 m (24 in.) spacing" (page 69) provides the fastener
locations for wood and metal stud walls with the maximum
allowed stud spacing of 0.6 m (24 in.).
Figure 23 "Plywood fastener locations for concrete and masonry
walls" (page 70) provides the fastener locations for concrete and
masonry walls.
Nortel Communication Server 1000
Communication Server 1000M and Meridian 1 Small System Installation and Commissioning
NN43011-310 01.04 Standard
Release 5.0 13 May 2008
Copyright © 2008, Nortel Networks
.
Vista de página 66
1 2 ... 62 63 64 65 66 67 68 69 70 71 72 ... 473 474

Comentários a estes Manuais

Sem comentários